range of product | Harmony Easy XA2 |
---|---|
product or component type | Complete emergency switching off push-button |
device short name | XA2 |
bezel material | Plastic |
mounting diameter | 22 mm |
operating position | Any position |
---|---|
device mounting | Fixing hole - diameter: 22 mm |
fixing center | >= 30 x 40 mm (panel) - thickness: 1…5 mm |
fixing mode | Fixing nut: 2…2.4 N.m |
shape of signaling unit head | Round |
type of operator | turn to release |
reset | Turn to release |
operator profile | Red mushroom Ø 40 mm |
contacts type and composition | 1 NC |
contact operation | Slow-break |
positive opening | With NC contact |
mechanical durability | 100000 cycles |
connections - terminals | Screw clamp terminal, <= 2 x 1.5 mm² Screw clamp terminal, <= 1 x 2.5 mm² Screw clamp terminal, >= 1 x 0.5 mm² Faston terminals, connection size: 6.3 mm |
tightening torque | 0.8 N.m |
short-circuit protection | 10 A gL fuse conforming to IEC 60269-1 |
[Ith] conventional free air thermal current | 10 A |
[Ui] rated insulation voltage | 600 V conforming to IEC 60947-1 |
[Uimp] rated impulse withstand voltage | IEC 60947-1 6 kV |
[Ie] rated operational current | 3 A at 240 V, AC-15, A600 0.27 A at 250 V, DC-13, Q600 |
electrical durability | 500000 cycles, AC-15, 3 A at 230 V, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-4 500000 cycles, DC-13, 0.2 A at 110 V, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-4 |
electrical reliability | Λ < 10exp(-8) at 24 V |
height | 30 mm |
width | 42 mm |
depth | 74.2 mm |
net weight | 0.058 kg |
protective treatment | TC |
---|---|
ambient air temperature for storage | -40…70 °C |
ambient air temperature for operation | -25…55 °C |
overvoltage category | Class I conforming to IEC 536 |
IP degree of protection | IP65 conforming to IEC 60529 |
IK degree of protection | IK03 conforming to IEC 60529 |
standards | IEC 60947-1 GB 14048.1 GB 14048.5 IEC 60947-5-1 |
product certifications | CCC CE |
vibration resistance | 10 gn (f= 40…500 Hz) conforming to IEC 60068-2-6 |
shock resistance | 70 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27 |