range of product | Harmony Relay |
---|---|
series name | Power |
product or component type | Plug-in relay |
device short name | RPM |
contacts type and composition | 4 C/O |
[Uc] control circuit voltage | 230 V AC |
[Ithe] conventional enclosed thermal current | 15 A at -40…55 °C |
status LED | With |
control type | Lockable test button |
utilisation coefficient | 20 % |
shape of pin | Flat |
---|---|
[Ui] rated insulation voltage | 250 V conforming to IEC 300 V conforming to CSA 300 V conforming to UL |
[Uimp] rated impulse withstand voltage | 4 kV during 1.2/50 µs |
contacts material | AgNi |
[Ie] rated operational current | 15 A at 277 V (AC) conforming to UL 15 A at 28 V (DC) conforming to UL 15 A at 250 V (AC) NO conforming to IEC 15 A at 28 V (DC) NO conforming to IEC 7.5 A at 250 V (AC) NC conforming to IEC 7.5 A at 28 V (DC) NC conforming to IEC |
maximum switching voltage | 250 V conforming to IEC |
Resistive load current | 15 A at 250 V AC 15 A at 28 V DC |
maximum switching capacity | 3750 VA 420 W |
minimum switching capacity | 170 mW at 10 mA, 17 V |
operating rate | <= 1200 cycles/hour under load <= 18000 cycles/hour no-load |
mechanical durability | 10000000 cycles |
electrical durability | 100000 cycles for resistive load |
Average coil consumption in VA | 2.5 at 60 Hz |
drop-out voltage threshold | >= 0.15 Uc AC |
Operate time | 20 ms at nominal voltage |
Release time | 20 ms at nominal voltage |
Average coil resistance | 7350 Ohm at 20 °C +/- 15 % |
rated operational voltage limits | 184...253 V AC |
protection category | RT I |
test levels | Level A group mounting |
operating position | Any position |
pollution degree | 3 |
safety reliability data | B10d = 100000 |
net weight | 0.071 kg |
device presentation | Complete product |