range of product | Zelio Control |
---|---|
product or component type | Modular measurement and control relays |
relay type | Control relay |
product specific application | For 3-phase supply |
relay name | RM17TG |
relay monitored parameters | Phase sequence Phase failure detection (2 or more phase cut) |
time delay | Without |
switching capacity in VA | 1250 VA |
measurement range | 208...440 V voltage AC |
maximum switching voltage | 250 V AC 250 V DC |
---|---|
minimum switching current | 10 mA at 5 V DC |
supply voltage limits | 183…484 V AC |
control circuit voltage limits | - 12 % + 10 % Un |
power consumption in VA | 0…22 VA at 400 V AC 50 Hz |
voltage detection threshold | < 100 V AC |
control circuit frequency | 50...60 Hz +/- 10 % |
output contacts | 2 C/O |
nominal output current | 5 A |
measurement voltage limits | 183…484 V AC |
delay at power up | 650 ms |
voltage range | 183...484 V |
response time | <= 130 ms (in the event of a fault) |
marking | CE |
overvoltage category | III conforming to IEC 60664-1 |
insulation resistance | > 500 MOhm at 500 V DC conforming to IEC 60255-5 > 500 MOhm at 500 V DC conforming to IEC 60664-1 |
[Ui] rated insulation voltage | 400 V conforming to IEC 60664-1 |
supply frequency | 50/60 Hz +/- 10 % |
operating position | Any position without derating |
connections - terminals | Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end |
tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
housing material | Self-extinguishing plastic |
local signalling | LED (yellow) for relay ON |
mounting support | 35 mm symmetrical DIN rail conforming to EN/IEC 60715 |
electrical durability | 10000 cycles |
mechanical durability | 30000000 cycles |
operating rate | <= 360 operations/hour full load |
utilisation category | AC-12 conforming to IEC 60947-5-1 AC-13 conforming to IEC 60947-5-1 AC-14 conforming to IEC 60947-5-1 AC-15 conforming to IEC 60947-5-1 DC-12 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 |
safety reliability data | B10d = 850000 MTTFd = 924.6 years |
width | 17.5 mm |
net weight | 0.13 kg |