range | Compact |
---|---|
product name | Compact NSX |
product or component type | Circuit breaker |
device short name | Compact NSX630H |
device application | Distribution |
poles description | 3P |
protected poles description | 3t |
network type | AC |
network frequency | 50/60 Hz |
[In] rated current | 630 A ( 40 °C ) |
[Ui] rated insulation voltage | 800 V AC 50/60 Hz |
[Uimp] rated impulse withstand voltage | 8 kV |
[Ue] rated operational voltage | 690 V AC 50/60 Hz |
breaking capacity code | H (70 kA) AC |
breaking capacity | 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 600 V AC 50/60 Hz conforming to UL 508 65 kA at 480 V AC 50/60 Hz conforming to UL 508 85 kA at 240 V AC 50/60 Hz conforming to UL 508 |
[Ics] rated service breaking capacity | Ics 10 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2 Ics 100 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2 Ics 11 kA 525 V AC 50/60 Hz conforming to IEC 60947-2 Ics 50 kA 500 V AC 50/60 Hz conforming to IEC 60947-2 Ics 65 kA 440 V AC 50/60 Hz conforming to IEC 60947-2 Ics 70 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2 |
suitability for isolation | Yes conforming to EN 60947-2 Yes conforming to IEC 60947-2 |
utilisation category | Category A |
trip unit name | Micrologic 2.3 |
trip unit technology | Electronic |
trip unit protection functions | LSoI |
trip unit rating | 630 A ( 40 °C ) |
protection type | Overload protection (long time) L Short time short-circuit protection with fixed delay So Instantaneous short-circuit protection I |
pollution degree | 3 conforming to IEC 60664-1 |
control type | Toggle |
---|---|
mounting mode | Fixed |
mounting support | Backplate |
upside connection | Front |
downside connection | Front |
auxiliary contact composition | Without |
mechanical durability | 15000 cycles |
electrical durability | 2000 cycles 690 V In conforming to IEC 60947-2 4000 cycles 440 V In conforming to IEC 60947-2 6000 cycles 690 V In/2 conforming to IEC 60947-2 8000 cycles 440 V In/2 conforming to IEC 60947-2 |
connection pitch | 45 mm |
local signalling | LED 105 % Ir LED 90 % Ir LED ready |
long time pick-up adjustment type Ir | Adjustable 9 settings |
long time pick-up adjustment range | 0.9...1 x Io |
long time delay adjustment type | Fixed |
[tr] long-time delay adjustment range | 16 s 6 x Ir |
thermal memory | 20 minutes before and after tripping |
short-time pick-up adjustment type Isd | Adjustable 9 settings |
[Isd] short-time pick-up adjustment range | 1.5...10 x Ir |
short-time delay adjustment type | Fixed |
instantaneous pick-up adjustment type Ii | Fixed |
instantaneous pick-up adjustment range | 6900 A |
height | 255 mm |
width | 140 mm |
depth | 110 mm |
product weight | 6.2 kg |
overvoltage category | Class II |
---|---|
electrical shock protection class | Class II |
standards | EN/IEC 60947 UL 508 |
product certifications | CCC Marine EAC |
IP degree of protection | IP40 conforming to IEC 60529 |
IK degree of protection | IK07 conforming to IEC 62262 |
ambient air temperature for operation | -35...70 °C |
ambient air temperature for storage | -55...85 °C |