range | Compact |
---|---|
product name | Compact NSX |
product or component type | Circuit breaker |
device short name | Compact NSX100F |
device application | Distribution |
poles description | 3P |
protected poles description | 3t |
network type | AC |
network frequency | 50/60 Hz |
[In] rated current | 100 A ( 40 °C ) |
[Ui] rated insulation voltage | 800 V AC 50/60 Hz |
[Uimp] rated impulse withstand voltage | 8 kV |
[Ue] rated operational voltage | 690 V AC 50/60 Hz |
breaking capacity code | F (36 kA) AC |
breaking capacity | 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 600 V AC 50/60 Hz conforming to UL 508 25 kA at 480 V AC 50/60 Hz conforming to UL 508 85 kA at 240 V AC 50/60 Hz conforming to UL 508 |
[Ics] rated service breaking capacity | Ics 11 kA 525 V AC 50/60 Hz conforming to IEC 60947-2 Ics 35 kA 440 V AC 50/60 Hz conforming to IEC 60947-2 Ics 36 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2 Ics 4 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2 Ics 85 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2 Ics 12.5 kA 500 V AC 50/60 Hz conforming to IEC 60947-2 |
suitability for isolation | Yes conforming to EN 60947-2 Yes conforming to IEC 60947-2 |
utilisation category | Category A |
trip unit name | TM-D |
trip unit technology | Thermal-magnetic |
trip unit protection functions | LI |
trip unit rating | 32 A ( 40 °C ) |
protection type | Overload protection (thermal) L Short-circuit protection (magnetic) I |
pollution degree | 3 conforming to IEC 60664-1 |
control type | Toggle |
---|---|
mounting mode | Fixed |
mounting support | Backplate |
upside connection | Front |
downside connection | Front |
auxiliary contact composition | Without |
mechanical durability | 50000 cycles |
electrical durability | 10000 cycles 690 V In conforming to IEC 60947-2 20000 cycles 690 V In/2 conforming to IEC 60947-2 30000 cycles 440 V In conforming to IEC 60947-2 50000 cycles 440 V In/2 conforming to IEC 60947-2 |
connection pitch | 35 mm |
local signalling | Positive contact indication |
long time pick-up adjustment type Ir | Adjustable |
long time pick-up adjustment range | 0.7...1 x In |
long time delay adjustment type | Fixed |
[tr] long-time delay adjustment range | 15 s 6 x Ir 120...400 s 1.5 x In |
short-time pick-up adjustment type Isd | Fixed |
[Isd] short-time pick-up adjustment range | 400 A |
short-time delay adjustment type | Fixed |
height | 161 mm |
width | 105 mm |
depth | 86 mm |
product weight | 2.05 kg |
overvoltage category | Class II |
---|---|
electrical shock protection class | Class II |
standards | EN/IEC 60947 UL 508 |
product certifications | CCC Marine EAC |
IP degree of protection | IP40 conforming to IEC 60529 |
IK degree of protection | IK07 conforming to IEC 62262 |
ambient air temperature for operation | -35...70 °C |
ambient air temperature for storage | -55...85 °C |