range | TeSys |
---|---|
product name | TeSys F |
product or component type | Contactor |
device short name | LC1F |
contactor application | Motor control Resistive load |
utilisation category | AC-1 AC-3 AC-4 |
poles description | 3P |
power pole contact composition | 3 NO |
[Ue] rated operational voltage | <= 690 V AC 50/60 Hz |
[Ie] rated operational current | 275 A (<= 40 °C) at <= 440 V AC-1 185 A (<= 55 °C) at <= 440 V AC-3 |
motor power kW | 90 kW at 380...400 V AC 50/60 Hz AC-3 100 kW at 415 V AC 50/60 Hz AC-3 100 kW at 440 V AC 50/60 Hz AC-3 110 kW at 500 V AC 50/60 Hz AC-3 110 kW at 660...690 V AC 50/60 Hz AC-3 33 kW at 400 V AC 50/60 Hz AC-4 55 kW at 220...240 V AC 50/60 Hz AC-3 |
[Uimp] rated impulse withstand voltage | 8 kV |
---|---|
overvoltage category | III |
[Ith] conventional free air thermal current | 275 A at <= 40 °C |
Irms rated making capacity | 1850 A conforming to IEC 60947-4-1 |
rated breaking capacity | 1480 A conforming to IEC 60947-4-1 |
[Icw] rated short-time withstand current | 1500 A <= 40 °C 10 s 920 A <= 40 °C 30 s 740 A <= 40 °C 1 min 500 A <= 40 °C 3 min 400 A <= 40 °C 10 min |
associated fuse rating | 200 A aM at <= 440 V 315 A gG at <= 440 V |
average impedance | 0.33 mOhm at 50 Hz - Ith 275 A |
[Ui] rated insulation voltage | 1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C |
power dissipation per pole | 12 W AC-3 25 W AC-1 |
mounting support | Plate |
standards | EN 60947-1 EN 60947-4-1 IEC 60947-1 IEC 60947-4-1 JIS C8201-4-1 |
product certifications | ABS BV CSA DNV LROS (Lloyds register of shipping) RINA RMRoS UL CB |
connections - terminals | Power circuit : connector 1 cable(s) 150 mm² Power circuit : lugs-ring terminals 1 cable(s) 150 mm² Power circuit : bolted connection Power circuit : bar 2 x (25 x 3 mm) |
tightening torque | Power circuit : 18 N.m |
IP degree of protection | IP2x front face with shrouds (ordered separately) conforming to IEC 60529 IP2x front face with shrouds (ordered separately) conforming to VDE 0106 |
---|---|
protective treatment | TH |
ambient air temperature for operation | -5...55 °C |
ambient air temperature for storage | -60...80 °C |
permissible ambient air temperature around the device | -40...70 °C |
operating altitude | 3000 m without derating |
mechanical robustness | Vibrations resistance contactor open 2 Gn, 5...300 Hz Vibrations resistance contactor closed 5 Gn, 5...300 Hz Shocks resistance contactor closed 15 Gn for 1/2 sine wave (11 ms) Shocks resistance contactor open 7 Gn for 1/2 sine wave (11 ms) |
height | 174 mm |
width | 168.5 mm |
depth | 181 mm |
product weight | 5.45 kg |