range | EasyPact |
---|---|
product name | EasyPact TVS |
product or component type | Contactor |
device short name | LC1E |
contactor application | Resistive load Motor control |
utilisation category | AC-1 AC-3 |
poles description | 3P |
power pole contact composition | 3 NO |
[Ue] rated operational voltage | Power circuit: <= 690 V AC 50/60 Hz |
[Ie] rated operational current | 65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit |
motor power kW | 18.5 kW at 220...230 V AC 50/60 Hz 30 kW at 380...400 V 37 kW at 415 V 37 kW at 440 V 37 kW at 500 V 37 kW at 660...690 V |
control circuit type | AC at 50/60 Hz |
[Uc] control circuit voltage | 220 V AC 50/60 Hz |
height | 127 mm |
width | 75 mm |
depth | 114 mm |
net weight | 0.98 kg |
colour | Grey (RAL 7011) |
auxiliary contact composition | 1 NO + 1 NC |
---|---|
[Uimp] rated impulse withstand voltage | 6 kV coil not connected to the power circuit conforming to IEC 60947 |
[Ui] rated insulation voltage | 690 V conforming to IEC 60947-4-1 |
overvoltage category | III |
Irms rated making capacity | 650 A at 440 V AC for power circuit conforming to IEC 60947-4-1 |
rated breaking capacity | 520 A at 440 V for power circuit conforming to IEC 60947 |
[Icw] rated short-time withstand current | 520 A 40 °C - 10 s for power circuit 260 A 40 °C - 60 s for power circuit 110 A 40 °C - 600 s for power circuit |
associated fuse rating | 10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1 125 A gG at <= 690 V coordination type 1 for power circuit |
average impedance | 1 mOhm - Ith 80 A 50 Hz for power circuit |
power dissipation per pole | 4.2 W AC-3 6.4 W AC-1 |
control circuit voltage limits | Operational: 0.85...1.1 Uc at 50/60 Hz (at <55 °C) Drop-out: 0.3...0.6 Uc at 50/60 Hz (at <55 °C) |
operating time | 20...26 ms on closing 8...12 ms on opening |
mechanical durability | 5000000 cycles |
maximum operating rate | 1200 cyc/h 60 °C |
inrush power in VA | 160 VA 50 Hz cos phi 0.75 (at 20 °C) 140 VA 60 Hz cos phi 0.75 (at 20 °C) |
hold-in power consumption in VA | 15 VA 50 Hz cos phi 0.3 (at 20 °C) 13 VA 60 Hz cos phi 0.3 (at 20 °C) |
heat dissipation | 6…10 W for control circuit |
minimum switching current | 5 mA for control circuit |
minimum switching voltage | 17 V for control circuit |
non-overlap time | 1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact |
insulation resistance | > 10 MOhm for control circuit |
electrical durability | 350000 cycles AC-1 900000 cycles AC-3 |
mounting support | DIN rail Plate |
connections - terminals | Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end Power circuit: screw clamp terminals 1 2.5…25 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 2.5…25 mm² - cable stiffness: solid without cable end Power circuit: screw clamp terminals 2 2.5…16 mm² - cable stiffness: solid without cable end |
Recommended tightening torque | Control circuit: 1.2 N.m Power circuit: 5 N.m |