range | TeSys |
---|---|
product name | TeSys LC1D.K |
product or component type | Capacitor duty contactor |
device short name | LC1DTK |
contactor application | Power factor correction |
utilisation category | AC-6B |
poles description | 3P |
power pole contact composition | 3 NO |
device location in system | Line interruption Inside delta interruption |
[Ue] rated operational voltage | <= 690 V AC 50/60 Hz for power circuit |
reactive power rating | 22 kvar at 230 V AC 50/60 Hz <= 60 °C 43 kvar at 440 V AC 50/60 Hz <= 60 °C 67 kvar at 660...690 V AC 50/60 Hz <= 60 °C 40 kvar at 400...415 V AC 50/60 Hz <= 60 °C |
control circuit type | AC 50/60 Hz |
[Uc] control circuit voltage | 220 V AC 50/60 Hz |
auxiliary contact composition | 1 NO + 2 NC for signalling circuit 3 NO early make for power circuit |
electrical durability | 300000 cycles at Ue 400 V 200000 cycles at Ue 690 V |
mounting support | DIN rail Plate |
standards | IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 |
product certifications | CCC CSA IEC UL EAC KC |
connections - terminals | Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable end Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable end Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable end Power circuit : screw clamp terminals 1 cable(s) 1...35 mm² - cable stiffness: solid - without cable end Power circuit : screw clamp terminals 2 cable(s) 1...25 mm² - cable stiffness: solid - without cable end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - with or without cable end Power circuit : screw clamp terminals 1 cable(s) 1...35 mm² - cable stiffness: flexible - with or without cable end Power circuit : screw clamp terminals 2 cable(s) 1...25 mm² - cable stiffness: flexible - with or without cable end |
tightening torque | Control circuit : 1.7 N.m - on screw clamp terminals Power circuit : 5 N.m - on screw clamp terminals - cable 1...25 mm² Power circuit : 8 N.m - on screw clamp terminals - cable 35 mm² |
operating rate | 100 cyc/h |
auxiliary contacts type | Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1 Type mirror contact (1 NC) conforming to IEC 60947-4-1 |
---|
IP degree of protection | IP2x conforming to IEC 60529 IP2x conforming to VDE 0106 |
---|---|
protective treatment | TH conforming to IEC 60068-2-30 |
ambient air temperature for operation | -5...60 °C |
ambient air temperature for storage | -60...80 °C |
operating altitude | 3000 m without derating |
height | 166 mm |
width | 55 mm |
depth | 156 mm |
product weight | 1.3 kg |