range | Acti 9 |
---|---|
product name | Acti 9 C60H-DC |
product or component type | Miniature circuit-breaker |
device short name | C60H-DC |
device application | Distribution |
poles description | 2P |
number of protected poles | 2 |
[In] rated current | 20 A at 25 °C |
network type | DC |
trip unit technology | Thermal-magnetic |
curve code | C |
breaking capacity | 10 kA Icu at 440 V DC conforming to EN 60947-2 10 kA Icu at 440 V DC conforming to IEC 60947-2 6 kA Icu at 500 V DC conforming to EN 60947-2 6 kA Icu at 500 V DC conforming to IEC 60947-2 20 kA Icu at 220 V DC conforming to GB 14048.2 20 kA Icu at 220 V DC conforming to IEC 60947-2 20 kA Icu at 250 V DC conforming to GB 14048.2 20 kA Icu at 250 V DC conforming to IEC 60947-2 |
utilisation category | Category A conforming to EN 60947-2 Category A conforming to IEC 60947-2 |
suitability for isolation | Yes conforming to IEC 60947-2 Yes conforming to EN 60947-2 |
network frequency | 50/60 Hz |
---|---|
[Ue] rated operational voltage | 500 V DC |
[Ics] rated service breaking capacity | 15 kA 75 % conforming to EN 60947-2 - 220 V DC 15 kA 75 % conforming to IEC 60947-2 - 220 V DC 15 kA 75 % conforming to EN 60947-2 - 250 V DC 15 kA 75 % conforming to IEC 60947-2 - 250 V DC 4.5 kA 75 % conforming to EN 60947-2 - 500 V DC 4.5 kA 75 % conforming to IEC 60947-2 - 500 V DC 7.5 kA 75 % conforming to EN 60947-2 - 440 V DC 7.5 kA 75 % conforming to IEC 60947-2 - 440 V DC |
[Ui] rated insulation voltage | 500 V DC conforming to IEC 60947-2 500 V DC conforming to EN 60947-2 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to EN 60947-2 6 kV conforming to IEC 60947-2 |
contact position indicator | Yes |
control type | Toggle |
local signalling | ON/OFF indication |
mounting mode | Fixed |
mounting support | 35 mm symmetrical DIN rail |
comb busbar and distribution block compatibility | Top or bottom: standard |
9 mm pitches | 4 |
net weight | 0.256 kg |
colour | White |
mechanical durability | 20000 cycles |
electrical durability | 3000 cycles 500 V DC 6000 cycles 500 V DC |
provision for padlocking | Padlockable |
locking options description | In position O |
tightening torque | Power circuit: 2.5 N.m top or bottom |
earth-leakage protection | Without |
standards | EN 60947-2 IEC 60947-2 |
---|---|
pollution degree | 3 conforming to EN 60947-2 3 conforming to IEC 60947-2 |
overvoltage category | IV |
tropicalisation | 2 conforming to IEC 60068-2 |
operating altitude | 2000 m |
ambient air temperature for operation | -25…70 °C |
ambient air temperature for storage | -40…85 °C |