SCHNEIDER - KWH METER IEM3255

Category: KWHMETER
No Referensi: A9MEM3255-TERA
HUBUNGI KAMI

Call / Whatsapp:


Whatsapp Only:


Tokopedia:

Main
range
Acti 9
range of product
Acti 9 iEM3000
device short name
IEM3255
product or component type
Energy meter
Complementary
poles description
3P + N
1P + N
3P
type of measurement
Active and reactive energy
Active and reactive power
Current
Voltage
metering type
Active, reactive, apparent energy (signed, four quadrant)
device application
Multi-tariff
Partial meter
Sub billing
accuracy class
Class 0.5S active energy conforming to IEC 62053-22
Class 0.5S active energy conforming to IEC 61557-12
Class C active energy conforming to EN 50470-3
input type
External CT 1 A or 5 A
[In] rated current
5 A
1 A
rated voltage
100…277 V
173…480 V
network frequency
60 Hz
50 Hz
technology type
Electronic
display type
LCD display
sampling rate
32 samples/cycle
measurement current
1…32767000 mA
maximum value measured
99999999 MWh
tariff input
Tariff (4)
communication port protocol
Modbus RTU at 9.6, 19.2 and 38.4 kbauds even/odd or none, insulation 4000 V
communication port support
Screw terminal block: RS485
local signalling
Green indicator light: power ON
Yellow flashing LED: accuracy checking
alarm: overload
Yellow indicator light: communications are active on the Modbus port (Modbus)
number of inputs
1 digital 0...5 V/11...40 V 24 V DC
number of outputs
1 digital (static)
output voltage
5...40 V DC 50 mA
mounting mode
Clip-on
mounting support
DIN rail
connections - terminals
Current circuit: screw terminals 6 mm² cable(s) 
Voltage circuit: screw terminals 2.5 mm² cable(s)
overvoltage category
III
standards
IEC 61036
IEC 62053-23
UL 61010-1
IEC 61010
IEC 62053-22
IEC 61557-12
product certifications
CE conforming to IEC 61010 (safety)
CE conforming to EN 61557-12 (power monitor)
CE conforming to IEC 61326-1 (EMC)
CULus conforming to UL 61010 (safety)
CULus conforming to ANSI C12.20 (sub-meter)
EAC (sub-meter)
RCM conforming to NMI M 6-1 (sub-meter)
UL
MID conforming to EN 50470-3 (sub-meter)
MID conforming to EN 62052 (sub-meter)
Environment
IP degree of protection
Front panel: IP40 conforming to IEC 60529
Body: IP20 conforming to IEC 60529
pollution degree
2
relative humidity
5…95 % at 50 °C
ambient air temperature for operation
-25…55 °C - MID
-25…60 °C - NMI
-25…60 °C - IEC
ambient air temperature for storage
-40…85 °C
operating altitude
< 2000 m
colour
White
9 mm pitches
10
width
90 mm
height
95 mm
depth
69 mm