SCHNEIDER - POWERTAG ENERGY M63 1PN TOP

Category: KWHMETER
No Referensi: A9MEM1521
HUBUNGI KAMI

Call / Whatsapp:


Whatsapp Only:


Tokopedia:

Main
Range of product
PowerLogic
product name
PowerTag A9 M63
product or component type
Energy sensor
Poles
1P + N
Maximum current [Imax]
63 A
[Ib] basic current
10 A
starting current
40 mA
saturation current
130 A
product specific application
Overload alarm
Cost allocation
Circuit monitoring
Load monitoring
Energy management
Concentrator compatibility
Acti9 Smartlink SI B
Acti9 Smartlink SI D
Acti9 PowerTag Link C
Acti9 PowerTag Link
Acti9 PowerTag Link HD
range compatibility
Acti 9 iKQE RCBO
Multi 9 C60
Multi 9 ID
Multi 9 C32N
Multi 9 C65
Acti 9 iID
Acti 9 iID K
Acti 9 iK60
Acti 9 iKQ
Acti 9 K60
Acti 9 Reflex iC60
Acti 9 iC65
Acti 9 DT60
Acti 9 iC60 single terminal
type of measurement
Power factor
Current
Active energy
Active power
Voltage
accuracy class
Class 1 current conforming to IEC 61557-12
Class 0.5 voltage conforming to IEC 61557-12
Class 1 active power conforming to IEC 61557-12
Class 1 active energy conforming to IEC 61557-12
Class 1 power factor conforming to IEC 61557-12
mounting location
Top
mounting support
On circuit breaker
product destination
Switchboard
Event management
Voltage loss with measured current at voltage loss
transmission support medium
Radio frequency 2.4…2.4835 GHz conforming to IEEE 802.15.4
maximum emission power
10 mW
Complementary
mounting mode
By screws (terminals)
Electrical connection (voltage sensing & power supply)
Connector tooth
cable cross section
1 rigid cable 1.5…16 mm²
2 stranded cable 1.5…2.5 mm²
2 rigid cable 1.5…2.5 mm²
1 stranded cable 1.5…16 mm²
supply voltage
200...240 V AC, +/- 20 %
network frequency
50 Hz
60 Hz
Maximum power consumption
1 VA
standards
IEC 61557-12
IEC 61010-1
IEC 61010-2-030
IEC 61326-1
ETSI EN 300 328
height
16.5 mm
width
36 mm
depth
43 mm
net weight
17.5 g
colour
White (RAL 9003)
Environment
quality labels
CE
directives
2014/53/EU - radio equipment directive
operating altitude
0...2000 m
ambient air temperature for operation
-25…60 °C
ambient air temperature for storage
-40…85 °C
overvoltage category
III conforming to IEC 61010-1
measurement category
Category III conforming to IEC 61010-2-030
IP degree of protection
IP20 conforming to IEC 60529
IK degree of protection
IK05
pollution degree
3
relative humidity
0…95 % at 45 °C conforming to IEC 60721-3-3
vibration resistance
3M4 conforming to IEC 60721-3-3
environmental characteristics
Dustproof class 3S3 conforming to IEC 60721-3-3
Salt mist class 3C2 conforming to IEC 60721-3-3
Indoor use