range | EasyPact |
---|---|
product name | EasyPact TVS |
product or component type | Contactor |
device short name | LC1E |
contactor application | Motor control Resistive load |
utilisation category | AC-3 AC-1 |
poles description | 3P |
power pole contact composition | 3 NO |
[Ue] rated operational voltage | Power circuit: <= 690 V AC 50/60 Hz |
[Ie] rated operational current | 95 A (at <60 °C) at <= 440 V AC AC-3 for power circuit 125 A (at <60 °C) at <= 440 V AC AC-1 for power circuit |
motor power kW | 45 kW at 415 V 45 kW at 440 V 45 kW at 500 V 25 kW at 220...230 V AC 50/60 Hz 45 kW at 380...400 V 55 kW at 660...690 V |
control circuit type | AC at 50/60 Hz |
[Uc] control circuit voltage | 220 V AC 50/60 Hz |
height | 127 mm |
width | 85 mm |
depth | 121 mm |
net weight | 1.52 kg |
colour | Grey (RAL 7011) |
auxiliary contact composition | 1 NO + 1 NC |
---|---|
[Uimp] rated impulse withstand voltage | 6 kV coil not connected to the power circuit conforming to IEC 60947 |
[Ui] rated insulation voltage | 690 V conforming to IEC 60947-4-1 |
overvoltage category | III |
Irms rated making capacity | 950 A at 440 V AC for power circuit conforming to IEC 60947-4-1 |
rated breaking capacity | 760 A at 440 V for power circuit conforming to IEC 60947 |
[Icw] rated short-time withstand current | 135 A 40 °C - 600 s for power circuit 800 A 40 °C - 10 s for power circuit 400 A 40 °C - 60 s for power circuit |
associated fuse rating | 10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1 160 A gG at <= 690 V coordination type 1 for power circuit |
average impedance | 0.8 mOhm - Ith 120 A 50 Hz for power circuit |
power dissipation per pole | 7.2 W AC-3 12 W AC-1 |
control circuit voltage limits | Operational: 0.85...1.1 Uc at 50/60 Hz (at <55 °C) Drop-out: 0.3...0.6 Uc at 50/60 Hz (at <55 °C) |
operating time | 20...35 ms on closing 6...30 ms on opening |
mechanical durability | 300000 cycles |
maximum operating rate | 1200 cyc/h 60 °C |
inrush power in VA | 200 VA 50 Hz cos phi 0.75 (at 20 °C) 220 VA 60 Hz cos phi 0.75 (at 20 °C) |
hold-in power consumption in VA | 22 VA 60 Hz cos phi 0.3 (at 20 °C) 20 VA 50 Hz cos phi 0.3 (at 20 °C) |
heat dissipation | 6…10 W for control circuit |
minimum switching current | 5 mA for control circuit |
minimum switching voltage | 17 V for control circuit |
non-overlap time | 1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact |
insulation resistance | > 10 MOhm for control circuit |
electrical durability | 350000 cycles AC-3 900000 cycles AC-1 |
mounting support | Plate DIN rail |
connections - terminals | Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end Power circuit: screw clamp terminals 1 4…50 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 4…16 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 4…50 mm² - cable stiffness: solid without cable end Power circuit: screw clamp terminals 2 4…50 mm² - cable stiffness: solid without cable end |
Recommended tightening torque | Control circuit: 1.2 N.m Power circuit: 12 N.m |
Max tightening torque | Control circuit: 1.4 N.m Power circuit: 13.5 N.m |