range | PowerLogic |
---|---|
product name | PowerLogic PM5000 |
device short name | PM5560 |
product or component type | Power meter |
power quality analysis | Up to the 63rd harmonic |
---|---|
metering type | Calculated ground current Measured neutral current |
device application | WAGES metering Power monitoring Gateway Multi-tariff |
type of measurement | Energy Active and reactive power Voltage Current Frequency Power factor |
supply voltage | 125...250 V DC 100...480 V AC (45...65 Hz) |
network frequency | 50 Hz 60 Hz |
[In] rated current | 1 A 5 A |
type of network | 1P + N 3P 3P + N |
power consumption in VA | <= 10 VA at 480 V |
ride-through time | 35 ms 120 V AC typical 129 ms 230 V AC typical |
display type | Backlit LCD |
display resolution | 128 x 128 pixels |
sampling rate | 128 samples/cycle |
measurement current | 5...10000 mA |
analogue input type | Current (impedance 0.3 mOhm) Voltage (impedance 5 MOhm) |
measurement voltage | 20...400 V AC 45...65 Hz between phase and neutral 20...690 V AC 45...65 Hz between phases |
frequency measurement range | 45...65 Hz |
number of inputs | 4 digital |
measurement accuracy | +/- 0.5 % apparent power +/- 0.05 % frequency +/- 0.2 % active energy +/- 1 % reactive energy +/- 0.2 % active power +/- 0.1 % voltage +/- 0.05 % power factor +/- 0.15 °C current |
accuracy class | Class 0.2S (active energy according to IEC 62053-22) |
number of outputs | 2 digital |
information displayed | Tariff 8 |
communication port protocol | Modbus RTU and ASCII 2 wires, : 9.6, 19.2 and 38.4 kbauds, even/odd or none, insulation: 2500 V JBUS Modbus TCP/IP : 10/100 Mbit/s, insulation: 2500 V Ethernet Modbus TCP/IP daisy chain BACnet IP |
communication port support | RS485 Ethernet |
communication gateway | Ethernet/serial |
data recording | Data logs Event logs Min/max of instantaneous values Time stamping Alarm logs Maintenance logs |
memory capacity | 1.1 MB |
web services | Alarm notification by e-mail Diagnostic via predefined web pages Web server Real time viewing of data |
Ethernet service | SNTP client SNMP-Traps |
connections - terminals | Voltage circuit: 4 screw terminal block Control circuit: 2 screw terminal block Current transformer: 6 screw terminal block RS485 link: 4 screw terminal block Digital input: 8 screw terminal block Digital output: 4 screw terminal block Ethernet network: 2 RJ45 connector |
mounting mode | Flush-mounted |
mounting support | Framework |
standards | IEC 60529 IEC 61557-12 IEC 62053-22 EN 50470-1 EN 50470-3 UL 61010-1 IEC 62053-24 |
product certifications | CE conforming to IEC 61010-1 CULus conforming to UL 61010-1 BTL |
width | 96 mm |
depth | 72 mm |
height | 96 mm |
product weight | 450 g |