range | ComPact |
---|---|
product name | ComPact NSX |
range of product | ComPact NSX100...250 |
device short name | NSX100N |
product or component type | Circuit breaker |
device application | Distribution |
Number of poles | 4P |
protected poles description | 3t |
neutral position | Left |
[In] rated current | 100 A at 40 °C |
[Ue] rated operational voltage | 690 V AC 50/60 Hz |
network type | AC |
network frequency | 50/60 Hz |
suitability for isolation | Yes conforming to EN/IEC 60947-2 |
utilisation category | Category A |
[Icu] rated ultimate short-circuit breaking capacity | 85 kA at 240 V AC 50/60 Hz conforming to UL 508 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 600 V AC 50/60 Hz conforming to UL 508 50 kA at 480 V AC 50/60 Hz conforming to UL 508 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
Performance level | N 50 kA 415 V AC |
trip unit name | TM-D |
trip unit technology | Thermal-magnetic |
trip unit protection functions | LI |
control type | Toggle |
Circuit breaker mounting mode | Fixed |
[Ui] rated insulation voltage | 800 V AC 50/60 Hz |
---|---|
[Uimp] rated impulse withstand voltage | 8 kV |
[Ics] rated service short-circuit breaking capacity | 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
mechanical durability | 50000 cycles |
electrical durability | 10000 cycles at 690 V In 20000 cycles at 690 V In/2 30000 cycles at 440 V In 50000 cycles at 440 V In/2 |
mounting support | Backplate |
upside connection | Front |
downside connection | Front |
connection pitch | 35 mm |
protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) |
trip unit rating | 100 A at 40 °C |
Long-time pick-up adjustment type Ir (thermal protection) | Adjustable |
[Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
Long-time protection delay adjustment type tr | Fixed |
[tr] long-time protection delay adjustment range | 120…400 s at 1.5 x In 15 s at 6 x Ir |
Short-time protection pick-up adjustment type Isd | Fixed |
[Isd] Short-time protection pick-up adjustment range | 800 A |
Short-time protection delay adjustment type tsd | Fixed |
earth-leakage protection | Without |
Neutral protection settings | No protection (3t) |
Number of slots for electrical auxiliaries | 5 slot(s) |
Width (W) | 140 mm |
Height (H) | 161 mm |
Depth (D) | 86 mm |
net weight | 2.4 kg |