range | ComPact |
---|---|
product name | ComPact NS |
range of product | ComPact NS630b...1600 |
device short name | Compact NS1250N |
product or component type | Circuit breaker |
device application | Distribution |
Number of poles | 4P |
protected poles description | 4d |
neutral position | Left |
(In) rated current up to 65 °C | 1250 A at 50 °C |
[Ue] rated operational voltage | 690 V AC 50/60 Hz |
network type | AC |
network frequency | 50/60 Hz |
suitability for isolation | Yes conforming to EN/IEC 60947-2 |
utilisation category | Category B |
[Icu] rated ultimate short-circuit breaking capacity | 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 |
Performance level | N 50 kA 415 V AC |
trip unit name | Micrologic 2.0 |
trip unit technology | Electronic |
trip unit protection functions | LI |
control type | Toggle Rotary handle |
Circuit breaker mounting mode | Fixed |
[Ui] rated insulation voltage | 800 V AC 50/60 Hz conforming to IEC 60947-2 |
---|---|
[Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
[Ics] rated service short-circuit breaking capacity | 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
[Icw] rated short-time withstand current | 19.2 kA 1 s conforming to IEC 60947-2 |
mechanical durability | 10000 cycles |
electrical durability | 2000 cycles at 690 V In 3000 cycles at 690 V In/2 4000 cycles at 440 V In 5000 cycles at 440 V In/2 |
power losses | 44 W |
mounting support | Backplate |
upside connection | Front |
downside connection | Front |
connection pitch | 70 mm |
protection type | L : for overload protection (long time) I : for instantaneous short-circuit protection |
trip unit rating | 1250 A at 50 °C |
Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
[Ir] long-time protection pick-up adjustment range | 0.4...1 x In |
Long-time protection delay adjustment type tr | Adjustable 9 settings |
[tr] long-time protection delay adjustment range | 12.5…600 s at 1.5 x Ir 0.5…24 s at 6 x Ir 0.7…16.6 s at 7.2 x Ir |
thermal memory | 20 mn |
Instantaneous protection pick-up adjustment type Ii | Adjustable |
[Ii] instantaneous protection pick-up adjustment range | 1.5...10 x Ir |
earth-leakage protection | Without |
Neutral protection settings | No protection (3d) 0.5 x Ir (3d + N/2) 1 x Ir (4d) |
auxiliary contact composition | 1 NO/NC |
local signalling | 4 LEDs (red) for fault indication 1 LED (yellow) for overload |
Width (W) | 280 mm |
Height (H) | 327 mm |
Depth (D) | 147 mm |
net weight | 18 kg |
standards | EN/IEC 60947-2 |
---|---|
product certifications | ASTA ASEFA |
pollution degree | 3 conforming to IEC 60947 |
IP degree of protection | IP40 conforming to IEC 60529 |
IK degree of protection | IK07 conforming to EN 50102 |
ambient air temperature for operation | -25…70 °C |
ambient air temperature for storage | -50…85 °C |
relative humidity | 0…95 % |
operating altitude | 0...2000 m without derating 2000 m...5000 m with derating |