SCHNEIDER - MINI KONTAKTOR / CONTACTOR 1NO 3P/12A 220V

Category: 3 POLE
No Referensi: LC1K1210M7
HUBUNGI KAMI

Call / Whatsapp:


Whatsapp Only:


Tokopedia:

Main
range
TeSys
product or component type
Contactor
product name
TeSys K
device short name
LC1K
device application
Control
contactor application
Motor control
Resistive load
Complementary
utilisation category
AC-1
AC-3
AC-4
poles description
3P
power pole contact composition
3 NO
[Ue] rated operational voltage
690 V AC 50/60 Hz for power circuit
<= 690 V AC 50/60 Hz for signalling circuit
[Ie] rated operational current
20 A (<= 50 °C) at <= 440 V AC AC-1 for power circuit
16 A (<= 70 °C) at 690 V AC AC-1 for power circuit
12 A at <= 440 V AC AC-3 for power circuit
control circuit type
AC 50/60 Hz
[Uc] control circuit voltage
220...230 V AC 50/60 Hz
motor power kW
3 kW at 220...230 V AC 50/60 Hz AC-3
2.2 kW at 400 V AC 50/60 Hz AC-4
5.5 kW at 440 V AC 50/60 Hz AC-3
5.5 kW at 380...415 V AC 50/60 Hz AC-3
4 kW at 480 V AC 50/60 Hz AC-3
4 kW at 500...600 V AC 50/60 Hz AC-3
4 kW at 660...690 V AC 50/60 Hz AC-3
auxiliary contact composition
1 NO
[Uimp] rated impulse withstand voltage
8 kV
overvoltage category
III
[Ith] conventional free air thermal current
20 A at <= 50 °C for power circuit
10 A at <= 50 °C for signalling circuit
Irms rated making capacity
110 A AC for signalling circuit conforming to IEC 60947
144 A AC for power circuit conforming to NF C 63-110
144 A AC for power circuit conforming to IEC 60947
rated breaking capacity
110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
70 A at 660...690 V conforming to IEC 60947
[Icw] rated short-time withstand current
25 A <= 50 °C >= 15 min power circuit
80 A 1 s signalling circuit
90 A 500 ms signalling circuit
110 A 100 ms signalling circuit
115 A <= 50 °C 1 s power circuit
105 A <= 50 °C 5 s power circuit
100 A <= 50 °C 10 s power circuit
75 A <= 50 °C 30 s power circuit
55 A <= 50 °C 1 min power circuit
50 A <= 50 °C 3 min power circuit
associated fuse rating
25 A gG at <= 440 V for power circuit
25 A aM for power circuit
10 A gG for signalling circuit conforming to IEC 60947
10 A gG for signalling circuit conforming to VDE 0660
average impedance
3 mOhm at 50 Hz - Ith 20 A for power circuit
[Ui] rated insulation voltage
690 V for signalling circuit conforming to IEC 60947-4-1
690 V for signalling circuit conforming to IEC 60947-5-1
600 V for signalling circuit conforming to UL 508
600 V for power circuit conforming to CSA C22.2 No 14
600 V for signalling circuit conforming to CSA C22.2 No 14
690 V for power circuit conforming to IEC 60947-4-1
600 V for power circuit conforming to UL 508
insulation resistance
> 10 MOhm for signalling circuit
inrush power in VA
30 VA at 20 °C
hold-in power consumption in VA
4.5 VA at 20 °C
heat dissipation
1.3 W
control circuit voltage limits
0.2...0.75 Uc at <= 50 °C drop-out
0.8...1.15 Uc at <= 50 °C operational
connections - terminals
Screw clamp terminals 1 cable(s) 1.5...4 mm² - cable stiffness: solid
Screw clamp terminals 1 cable(s) 0.75...4 mm² - cable stiffness: flexible - without cable end
Screw clamp terminals 1 cable(s) 0.34...2.5 mm² - cable stiffness: flexible - with cable end
Screw clamp terminals 2 cable(s) 1.5...4 mm² - cable stiffness: solid
Screw clamp terminals 2 cable(s) 0.75...4 mm² - cable stiffness: flexible - without cable end
Screw clamp terminals 2 cable(s) 0.34...1.5 mm² - cable stiffness: flexible - with cable end
operating rate
3600 cyc/h
auxiliary contacts type
Type instantaneous (1 NO)
signalling circuit frequency
<= 400 Hz
minimum switching current
5 mA for signalling circuit
minimum switching voltage
17 V for signalling circuit
mounting support
Plate
Rail
tightening torque
1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2
1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
operating time
10...20 ms coil de-energisation and NO opening
10...20 ms coil energisation and NO closing
safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
non overlap distance
0.5 mm
mechanical durability
10 Mcycles
electrical durability
0.3 Mcycles 20 A AC-1 at Ue <= 440 V
1.3 Mcycles 12 A AC-3 at Ue <= 440 V
mechanical robustness
Shocks contactor closed, on X axis 10 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on Y axis 15 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on Z axis 15 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on X axis 6 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Y axis 10 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Z axis 10 Gn for 11 ms IEC 60068-2-27
Vibrations contactor closed 4 Gn, 5...300 Hz IEC 60068-2-6
Vibrations contactor opened 2 Gn, 5...300 Hz IEC 60068-2-6
height
58 mm
width
45 mm
depth
57 mm
product weight