SCHNEIDER - MCCB EZC100H 3P 15A 30KA

Category: EASYPACT EZC
No Referensi: EZC100H3015
HUBUNGI KAMI

Call / Whatsapp:


Whatsapp Only:


Tokopedia:

Main
range of product
EasyPact
product or component type
Circuit breaker
device short name
Easypact EZC100H
circuit breaker name
Easypact EZC100H
device application
Distribution
poles description
3P
protected poles description
3t
network type
AC
DC
network frequency
50/60 Hz
[In] rated current
100 A ( 40 °C )
[Ui] rated insulation voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-2
[Ue] rated operational voltage
250 V DC conforming to IEC 60947-2
550 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity code
H
breaking capacity
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 125 V DC 1P conforming to IEC 60947-2
10 kA Icu at 250 V DC 2P conforming to IEC 60947-2
10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity
Ics 15 kA 380 V AC 50/60 Hz conforming to IEC 60947-2
Ics 5 kA 125 V DC conforming to IEC 60947-2
Ics 5 kA 250 V DC conforming to IEC 60947-2
Ics 5 kA 440 V AC 50/60 Hz conforming to IEC 60947-2
Ics 50 kA 110/130 V AC 50/60 Hz conforming to IEC 60947-2
Ics 50 kA 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
Ics 2.5 kA 550 V AC 50/60 Hz conforming to IEC 60947-2
Ics 7.5 kA 400/415 V AC 50/60 Hz conforming to IEC 60947-2
suitability for isolation
Yes conforming to IEC 60947-2
utilisation category
Category A
trip unit name
TM-D
trip unit technology
Thermal-magnetic
trip unit rating
15 A ( 50 °C )
protection type
Overload protection
Short-circuit protection
pollution degree
3 conforming to IEC 60664-1
3 conforming to IEC 947-1
Complementary
control type
Toggle
mounting mode
Fixed
mounting support
Backplate
upside connection
Front
downside connection
Front
mechanical durability
8500 cycles
electrical durability
Category A : 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
connection pitch
25 mm
local signalling
Positive contact indication
neutral protection setting
Without protection
earth-leakage protection
Without
height
130 mm
width
75 mm
depth
60 mm
Environment
standards
EN/IEC 60947-1
EN/IEC 60947-2
JIS C8201-2-2
GB/T 14048.2
IP degree of protection
IP20 conforming to IEC 60529
IK degree of protection
IK07 conforming to IEC 62262
ambient air temperature for operation
-25...70 °C
ambient air temperature for storage
-35...85 °C