range of product | EasyPact |
---|---|
product or component type | Circuit breaker |
device short name | Easypact EZC100B |
circuit breaker name | Easypact EZC100B |
device application | Distribution |
poles description | 3P |
protected poles description | 3t |
network type | AC DC |
network frequency | 50/60 Hz |
[In] rated current | 100 A ( 40 °C ) |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
[Ue] rated operational voltage | 550 V AC 50/60 Hz conforming to IEC 60947-2 |
breaking capacity code | B |
breaking capacity | 10 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ics] rated service breaking capacity | Ics 0.625 kA 550 V AC 50/60 Hz conforming to IEC 60947-2 Ics 1.25 kA 440 V AC 50/60 Hz conforming to IEC 60947-2 Ics 1.875 kA 380 V AC 50/60 Hz conforming to IEC 60947-2 Ics 1.875 kA 400/415 V AC 50/60 Hz conforming to IEC 60947-2 Ics 2.5 kA 110/130 V AC 50/60 Hz conforming to IEC 60947-2 Ics 2.5 kA 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 |
suitability for isolation | Yes conforming to IEC 60947-2 |
utilisation category | Category A |
trip unit name | TM-D |
trip unit technology | Thermal-magnetic |
trip unit rating | 30 A ( 50 °C ) |
protection type | Overload protection Short-circuit protection |
pollution degree | 3 conforming to IEC 60664-1 3 conforming to IEC 947-1 |
control type | Toggle |
---|---|
mounting mode | Fixed |
mounting support | Backplate |
upside connection | Front |
downside connection | Front |
mechanical durability | 8500 cycles |
electrical durability | Category A : 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2 |
connection pitch | 25 mm |
local signalling | Positive contact indication |
neutral protection setting | Without protection |
earth-leakage protection | Without |
height | 130 mm |
width | 75 mm |
depth | 60 mm |
standards | EN/IEC 60947-1 EN/IEC 60947-2 JIS C8201-2-2 GB/T 14048.2 |
---|---|
IP degree of protection | IP20 conforming to IEC 60529 |
IK degree of protection | IK07 conforming to IEC 62262 |
ambient air temperature for operation | -25...70 °C |
ambient air temperature for storage | -35...85 °C |