range | TeSys |
---|---|
product name | TeSys D |
device short name | LR97 |
product or component type | Electronic overcurrent relay |
relay application | Sensitivity to phase failure Overload Imax > Isetting Locked rotor, mechanical jamming I > 3 x Isetting |
product compatibility | LC1D09-D38 |
network type | AC |
[Us] rated supply voltage | 200-240 V AC |
thermal protection adjustment range | 0.3 - 1.5 A |
[Ue] rated operational voltage | 600 V AC 50/60 Hz for power circuit conforming to CSA 600 V AC 50/60 Hz for power circuit conforming to UL 690 V AC 50/60 Hz for power circuit conforming to IEC 60947-4-1 |
Quantity per set | Set of 10 |
network frequency | 50-60 Hz |
---|---|
mounting support | Direct on contactor Rail |
tripping threshold | 0.3-1.3 A |
surge withstand | 6 kV conforming to IEC 61000-4-5 |
contacts type and composition | 1 C/O |
[Ith] conventional free air thermal current | 3 A for control circuit |
protection type | BS fuse 3 A - for control circuit GB2 circuit breaker 3 A - for control circuit GG fuse 3 A - for control circuit |
maximum power | 28 W at 110 V DC conforming to IEC 60947 28 W at 220 V DC conforming to IEC 60947 55 W at 24 V DC conforming to IEC 60947 55 W at 48 V DC conforming to IEC 60947 140 VA at 48 V AC conforming to IEC 60947 360 VA at 110 V AC conforming to IEC 60947 360 VA at 220 V AC conforming to IEC 60947 70 VA at 24 V AC conforming to IEC 60947 |
[Ui] rated insulation voltage | Power circuit: 600 V conforming to CSA Power circuit: 600 V conforming to UL Power circuit: 690 V conforming to IEC 60947-4-1 |
[Uimp] rated impulse withstand voltage | 6 kV |
phase failure sensitivity | < 3 s |
reset | Automatic reset 120 s fixed Electrical by interruption of power supply for minimum 0.1 s Manual reset |
time range | 0.2-10 s - O-time knob 0.3-10 s - O-time knob 0.5..30 s - D-time knob |
signalling function | 2 LEDs |
connections - terminals | Control circuit: cable 1 x 1 - 25 mm²flexible with cable end Control circuit: cable 1 x 1 - 25 mm²flexible without cable end Power circuit: cable 1 x 1 - 4 mm²flexible with cable end Power circuit: cable 1 x 1.5 - 10 mm²flexible without cable end Power circuit: lug-clamp 1 x 1 - 4 mm²flexible with cable end Power circuit: lug-clamp 1 x 1.5 - 10 mm²flexible without cable end Control circuit: cable 2 x 1 - 25 mm²flexible with cable end Control circuit: cable 2 x 1 - 25 mm²flexible without cable end Control circuit: lug-clamp 1 x 1 - 25 mm²flexible with cable end Control circuit: lug-clamp 1 x 1 - 25 mm²flexible without cable end Control circuit: lug-clamp 2 x 1 - 25 mm²flexible with cable end Control circuit: lug-clamp 2 x 1 - 25 mm²flexible without cable end |
tightening torque | Control circuit: 0.6-1.2 N.m on lug-clamp Power circuit: 2 N.m on cable |
height | 67.5 mm |
width | 45 mm |
depth | 67.5 mm |
net weight | 0.172 kg |