SCHNEIDER - CONTACTOR 2P 16A 2NO 220VAC

Category: CIRCUIT BREAKER
No Referensi: A9C22512
HUBUNGI KAMI

Call / Whatsapp:


Whatsapp Only:


Tokopedia:

Main
range of product
Acti 9
product name
Acti 9 iCT
product or component type
Contactor
device short name
ICT
device application
Motor-heating-lighting
Poles
2P
[Ie] rated operational current
16 A AC-7A
6 A AC-7B
pole contact composition
2 NO
network type
AC
control type
Remote control
[Uc] control circuit voltage
220 V AC 50 Hz
Complementary
network frequency
50 Hz
[Ue] rated operational voltage
250 V AC 50 Hz
maximum power
1.3 W at 250 V AC
[Ui] rated insulation voltage
500 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
4 kV
control signal type
Maintained
switching frequency
100 switching operations/day
local signalling
Action indicator
hold-in power consumption in VA
3.8 VA
inrush power in VA
15 VA
mounting mode
Clip-on
mounting support
35 mm symmetrical DIN rail
9 mm pitches
2
height
81 mm
width
18 mm
depth
68.5 mm
colour
White
mechanical durability
1000000 cycles
electrical durability
100000 cycles IEC/EN 61095 16 A 50 Hz AC-7A
30000 cycles IEC/EN 61095 6 A 50 Hz AC-7B
30000 cycles IEC/EN 61095 50 Hz AC-7C
100000 cycles EN/IEC 60947-4-1 50 Hz AC-1
30000 cycles EN/IEC 60947-4-1 50 Hz AC-3
30000 cycles EN/IEC 60947-4-1 50 Hz AC-5a
30000 cycles EN/IEC 60947-4-1 50 Hz AC-5b
connections - terminals
Control circuit: tunnel type terminals2 cable(s) 1.5 mm² rigid
Power circuit: tunnel type terminals1 cable(s) 1…4 mm² flexible
Power circuit: tunnel type terminals1 cable(s) 1.5…6 mm² rigid
Control circuit: tunnel type terminals1 cable(s) 1.5…2.5 mm² rigid
Control circuit: tunnel type terminals2 cable(s) 1.5…2.5 mm² flexible
tightening torque
Control circuit: 0.8 N.m
Power circuit: 0.8 N.m
product compatibility
IACTs
compatibility code
ICT
market segment
Residential
Small commercial
Environment
standards
IEC/EN 61095
noise level
30 dB
heat dissipation
1.3 W
IP degree of protection
IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529
pollution degree
2
tropicalisation
2 conforming to EN 60947-4-1
2 conforming to EN 61095
2 conforming to IEC 1095
relative humidity
95 % at 55 °C
operating altitude
2000 m
ambient air temperature for operation
-5…60 °C
ambient air temperature for storage
-40…70 °C