range | Acti 9 |
---|---|
family | Acti 9 iEM2100 |
device short name | IEM2150 |
product or component type | Energy meter |
poles description | 1P + N |
---|---|
type of measurement | Active and reactive energy Active and reactive power Current Voltage |
metering type | Active, reactive, apparent energy (signed, four quadrant) |
device application | Sub billing Partial meter |
accuracy class | Class 1 active energy conforming to IEC 62053-21 Class 2 reactive energy conforming to IEC 62053-23 |
Input type | Direct input |
Rated current | 63 A |
rated voltage | 230 V +/- 20 % |
network frequency | 50 Hz 60 Hz |
frequency measurement range | 45…65 Hz |
technology type | Electronic |
display type | LCD display |
sampling rate | 32 samples/cycle |
measurement current | 0…63 A |
display digits | 8 |
maximum value measured | 999999.99 kWh |
Tariff input | Tariff (1) |
communication port protocol | Modbus RTU at 1.2, 2.4, 4.8, 9.6, 19.2 and 38.4 kbauds even/odd or none - 3 wires, insulation 4000 V |
communication port support | Screw terminals: RS485 |
local signalling | Red LED: accuracy checking 1...1000 p/kWh |
Digital inputs | 0 |
Digital outputs | 0 |
Supply voltage | 96...276 V AC 50 Hz |
maximum power consumption in VA | 2 VA |
maximum power consumption in W | 1 W |
[Uimp] rated impulse withstand voltage | 6 kV 1.2/50 µs |
mounting mode | Clip-on |
mounting support | DIN rail |
connections - terminals | Power circuit: tunnel type terminals (bottom) 1 1.65…33 mm² cable(s) solid Power circuit: tunnel type terminals (bottom) 1 1.65…33 mm² cable(s) stranded with cable end Communication: screw clamp terminals (top) 1 1…4 mm² cable(s) solid Communication: screw clamp terminals (top) 1 1…2.5 mm² cable(s) stranded with cable end |
tightening torque | Power circuit: 2 N.m PZ2 screwdriver Communication: 0.5 N.m3.5 mm |
wire stripping length | Power circuit: 17 mm Communication: 7 mm |
standards | IEC 62052-31 IEC 62053-21 IEC 62053-23 IEC 62052-11 |
product certifications | CE |