SCHNEIDER - SCREW TERMINAL CONTACT B 1NC

Category: LAIN - LAIN
No Referensi: ZB5AZ102
HUBUNGI KAMI

Call / Whatsapp:


Whatsapp Only:


Tokopedia:

Main
range of product
Harmony XB5
product or component type
Complete body/contact assembly
device short name
ZB5
fixing collar material
Plastic
sale per indivisible quantity
1
head type
Standard
contacts type and composition
1 NC
contact operation
Slow-break
contact block type
Single
connections - terminals
Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to EN 60947-1
Screw clamp terminals, >= 1 x 0.22 mm² without cable end conforming to EN 60947-1
Complementary
CAD overall width
30 mm
CAD overall height
42 mm
CAD overall depth
32 mm
terminals description ISO n°1
(11-12)NC
net weight
0.021 kg
device composition
Body
Fixing collar
contacts usage
Standard contacts
positive opening
With conforming to EN/IEC 60947-5-1 appendix K
operating travel
1.5 mm (NC changing electrical state)
4.3 mm (total travel)
operating force
2 N NC changing electrical state
mechanical durability
10000000 cycles
tightening torque
0.8…1.2 N.m conforming to EN 60947-1
shape of screw head
Cross compatible with Philips no 1 screwdriver
Cross compatible with pozidriv No 1 screwdriver
Slotted compatible with flat Ø 4 mm screwdriver
Slotted compatible with flat Ø 5.5 mm screwdriver
contacts material
Silver alloy (Ag/Ni)
short-circuit protection
10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
[Ith] conventional free air thermal current
10 A conforming to EN/IEC 60947-5-1
[Ui] rated insulation voltage
600 V (pollution degree 3) conforming to EN 60947-1
[Uimp] rated impulse withstand voltage
EN 60947-1 6 kV
[Ie] rated operational current
3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1
0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1
electrical durability
1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
electrical reliability
Λ < 10exp(-6) at 5 V, 1 mA in clean environment conforming to EN/IEC 60947-5-4
Λ < 10exp(-8) at 17 V, 5 mA in clean environment conforming to EN/IEC 60947-5-4
device presentation
Basic sub-assemblies