SCHNEIDER - POWER METER 8240 INTEGRATED DISPLAY, ACC 0.2, LAN/ETHERNET

Category: POWER METER
No Referensi: METSEPM8240
HUBUNGI KAMI

Call / Whatsapp:


Whatsapp Only:


Tokopedia:

Main
range
PowerLogic
product name
PowerLogic PM8000
device short name
PM8240
product or component type
Power meter
Complementary
power quality analysis
Waveform capture
Harmonic distortion
Programmablity (logic and math functions)
Voltage sag and swell detection
Up to the 63rd harmonic
Compliance report EN 50160
Power quality monitoring IEC 62586
Power quality measurement IEC 61000-4-30 : class S
device application
WAGES metering
Power monitoring
type of measurement
Power factor (total)
Apparent power (total)
Active and reactive power (total)
Active and reactive power (per phase, rms)
Apparent power (per phase, rms)
Power factor (per phase, rms)
Voltage
Current
Frequency
supply voltage
90...415 V AC +/- 10 % (45...65 Hz)
110...415 V DC +/- 10 %
network frequency
50 Hz
60 Hz
[In] rated current
1 A
10 A
5 A
poles description
1P + N
3P
3P + N
power consumption in VA
18 VA at 415 V AC
display type
Colour TFT LCD
display resolution
320 x 240 pixels QVGA
sampling rate
256 samples/cycle
measurement current
50...10000 mA
analogue input type
Current (impedance 0.3 mOhm)
Voltage (impedance 5 MOhm)
measurement voltage
57...400 V AC 42...69 Hz between phase and neutral
100...690 V AC 42...69 Hz between phases
frequency measurement range
42...69 Hz
number of inputs
3 digital 30 V AC
3 digital 60 V DC
measurement accuracy
+/- 0.2 % active energy
+/- 0.1 % voltage
+/- 0.1 % current
accuracy class
Class 0.2 (active energy according to ANSI C12.20)
Class 0.2S (active energy according to IEC 62053-22)
Class 0.2 (active power according to IEC 61557-12)
Class 0.5S (reactive energy according to IEC 62053-24)
Class 0.5 (power factor according to IEC 61557-12)
Class 0.2 (voltage according to IEC 61557-12)
Class 0.2 (current according to IEC 61557-12)
number of outputs
1 pulse
information displayed
Voltage
Current
Frequency
Power
Energy consumption
Harmonic distortion
communication port protocol
DNP3
IEC 61850
Modbus RTU 2-wire, : 115 kbauds,
ION 2-wire, : 115 kbauds,
Modbus TCP/IP
Ethernet Modbus TCP/IP daisy chain : 10/100 Mbit/s,
RSTP 801.1d 2004
communication port support
Ethernet
RS485 (screw terminal block)
communication network type
IPv6 (internet protocol)
data recording
Data logs
Event logs
Min/max of instantaneous values
Sequence of event recording
Time stamping
Trending/forecasting
GPS synchronisation
Alarm logs
Harmonics logs
Sag and swell logs
Waveform logs
memory capacity
512 MB
web services
Alarm notification by e-mail
File upload/download via FTP
HTTP server
Web server
Customizable home page
Viewing of captured waveform
communication service
DHCP
NTP time synchronization
SMTP e-mail notification
RSTP support
cybersecurity
Password protection
Port hardening
Robust security logs
Enable/disable communication ports
Syslog protocol support
mounting mode
Flush-mounted
mounting support
Framework
installation category
III
Safety Construction
IEC 61010-1 : CAT III, 400...690 V ed. 3
EN 61010-1 : CAT III, 400...690 V ed. 3
UL 61010-1 : CAT III, 347...600 V ed. 3
CSA C22.2 No 61010-1 : CAT III, 347...600 V ed. 3
standards
IEC 61557-12
IEC 62053-22
IEC 62052-11
IEC 62053-24
product certifications
N998
China RoHS
CULus
CE
width
96 mm
depth
77.5 mm
height
96 mm
product weight
581 g