range | PowerLogic |
---|---|
product name | PowerLogic PM5000 |
device short name | PM5330 |
product or component type | Power meter |
power quality analysis | Up to the 31st harmonic |
---|---|
device application | Power monitoring Multi-tariff |
type of measurement | Energy Active and reactive power Voltage Current Frequency Power factor |
supply voltage | 100...415 V AC (45...65 Hz) 125...250 V DC |
network frequency | 50 Hz 60 Hz |
[In] rated current | 1 A 5 A |
type of network | 1P + N 3P 3P + N |
power consumption in VA | <= 10 VA at 415 V |
ride-through time | 80 ms 120 V AC typical 100 ms 230 V AC typical 100 ms 415 V AC typical |
display type | Backlit LCD |
display resolution | 128 x 128 pixels |
sampling rate | 64 samples/cycle |
measurement current | 10...9000 mA |
analogue input type | Current (impedance 0.3 mOhm) Voltage (impedance 5 MOhm) |
measurement voltage | 35...690 V AC 45...65 Hz between phases 20...400 V AC 45...65 Hz between phase and neutral |
frequency measurement range | 45...65 Hz |
number of inputs | 2 digital |
measurement accuracy | +/- 0.5 % active energy +/- 2 % reactive energy +/- 0.5 % active power +/- 0.5 % apparent power +/- 0.05 % frequency +/- 0.005 % power factor +/- 0.5 % current +/- 0.5 % voltage |
accuracy class | Class 0.5S (active energy according to IEC 62053-22) |
number of outputs | 2 digital 2 relay |
information displayed | Tariff 4 |
communication port protocol | Modbus RTU and ASCII 2 wires, : 9.6, 19.2 and 38.4 kbauds, even/odd or none, insulation: 2500 V JBUS |
communication port support | RS485 |
data recording | Data logs Event logs Min/max of instantaneous values Time stamping Alarm logs Maintenance logs |
memory capacity | 256 kB |
connections - terminals | Voltage circuit: 4 screw terminal block Control circuit: 2 screw terminal block Current transformer: 6 screw terminal block Input/output circuit: 6 screw terminal block Relay output: 4 screw terminal block Ethernet network: RJ45 connector |
mounting mode | Flush-mounted |
mounting support | Framework |
standards | IEC 60529 IEC 61557-12 IEC 62053-22 EN 50470-1 EN 50470-3 UL 61010-1 IEC 62053-24 |
product certifications | CE conforming to IEC 61010-1 CULus conforming to UL 61010-1 |
width | 96 mm |
depth | 72 mm |
height | 96 mm |
product weight | 430 g |
electromagnetic compatibility | ● conducted and radiated emissions class class B, conforming to EN 55022 ● limits for harmonic current emissions class class A, conforming to IEC 61000-3-2 ● electrostatic discharge class level 4, conforming to IEC 61000-4-2 ● conducted RF disturbances class level 3, conforming to IEC 61000-4-6 ● magnetic field at power frequency class level 4, conforming to IEC 61000-4-8 |
---|---|
IP degree of protection | IP52 (front) conforming to IEC 60529 IP30 (body) conforming to IEC 60529 |
relative humidity | 5...95 % 50 °C |
pollution degree | 2 |
ambient air temperature for operation | -25...70 °C |
ambient air temperature for storage | -40...85 °C |
operating altitude | 2000 m |