SCHNEIDER - CONTACTOR CONTACTOR

Category: 3 POLE
No Referensi: LC1F1154
HUBUNGI KAMI

Call / Whatsapp:


Whatsapp Only:


Tokopedia:

TeSys F contactor - 4P(4 NO) - AC-1 - <= 440 V 200 A - without coil

 

Main
range
TeSys
product name
TeSys F
product or component type
Contactor
device short name
LC1F
contactor application
Resistive load
utilisation category
AC-1
poles description
4P
power pole contact composition
4 NO
[Ue] rated operational voltage
<= 690 V AC 50/60 Hz
[Ie] rated operational current
200 A (at <40 °C) at <= 440 V AC-1
Complementary
[Uc] control circuit voltage
24...575 V AC 40...400 Hz with LX9 coil
24...460 V DC with LX4 coil
100...250 V AC 50/60 Hz with LXE coil
100...380 V DC with LXE coil
[Uimp] rated impulse withstand voltage
8 kV
overvoltage category
III
[Ith] conventional free air thermal current
200 A (at 40 °C)
Irms rated making capacity
1150 A conforming to IEC 60947-4-1
rated breaking capacity
920 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
1100 A 40 °C - 10 s
640 A 40 °C - 30 s
520 A 40 °C - 1 min
400 A 40 °C - 3 min
320 A 40 °C - 10 min
associated fuse rating
200 A gG at <= 440 V
average impedance
0.37 mOhm - Ith 200 A 50 Hz
[Ui] rated insulation voltage
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
power dissipation per pole
15 W AC-1
control circuit voltage limits
Operational: 0.85...1.1 Uc AC 40...400 Hz with LX9 coil
Drop-out: 0.2...0.55 Uc AC 40...400 Hz with LX9 coil
Operational: 0.85...1.1 Uc DC with LX4 coil
Drop-out: 0.15...0.2 Uc DC with LX4 coil
Operational: 85...275 V AC 50/60 Hz with LXE coil
Drop-out: 0...60 V AC 50/60 Hz with LXE coil
Operational: 85...418 V DC with LXE coil
Drop-out: 0...45 V DC with LXE coil
heat dissipation
5.9…7.2 W
2.2…5.5 W
operating time
130 ms opening for with LX9 coil
30...40 ms closing for with LX4 coil
30...50 ms opening for with LX4 coil
40...80 ms closing for with LXE coil
6...54 ms opening for with LXE coil
mounting support
Plate
standards
EN 60947-4-1
IEC 60947-4-1
JIS C8201-4-1
EN 60947-1
IEC 60947-1
product certifications
CB
UL
RINA
DNV
LROS (Lloyds register of shipping)
RMRoS
CSA
ABS
BV
connections - terminals
Power circuit: lugs-ring terminals 1 cable(s) 95 mm²
Power circuit: connector 1 cable(s) 95 mm²
Power circuit: bar 2 cable(s) - busbar cross section: 20 x 3 mm
Power circuit: bolted connection
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²
Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²flexible without cable end
Control circuit: screw clamp terminals 1.0 cable(s) 0.25…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²solid without cable end
tightening torque
Power circuit: 10 N.m
Control circuit: 1.2 N.m
Control circuit: 0.6 N.m
inrush power in VA
590…855 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX9 coil
543…665 VA (at 20 °C)with LX4 coil
280…310 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil
270…320 VA (at 20 °C)with LXE coil
hold-in power consumption in VA
6.6…8.1 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX9 coil
3.94…4.83 VA (at 20 °C)with LX4 coil
4.5…7.0 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil
2.5…4.0 VA (at 20 °C)with LXE coil
maximum operating rate
2400 cyc/h 55 °C
compatibility code
LC1F