SCHNEIDER - TVS 3P CTR 400V 30KW 220V 50/60HZ

Category: 3 POLE
No Referensi: LC1E65M7
HUBUNGI KAMI

Call / Whatsapp:


Whatsapp Only:


Tokopedia:

EasyPact TVS contactor 3P(3 NO) - AC-3 - <= 440 V 65A - 220 V AC coil

 

Main
range
EasyPact
product name
EasyPact TVS
product or component type
Contactor
device short name
LC1E
contactor application
Resistive load
Motor control
utilisation category
AC-1
AC-3
poles description
3P
power pole contact composition
3 NO
[Ue] rated operational voltage
Power circuit: <= 690 V AC 50/60 Hz
[Ie] rated operational current
65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
motor power kW
18.5 kW at 220...230 V AC 50/60 Hz
30 kW at 380...400 V
37 kW at 415 V
37 kW at 440 V
37 kW at 500 V
37 kW at 660...690 V
control circuit type
AC at 50/60 Hz
[Uc] control circuit voltage
220 V AC 50/60 Hz
height
127 mm
width
75 mm
depth
114 mm
net weight
0.98 kg
colour
Grey (RAL 7011)
Complementary
auxiliary contact composition
1 NO + 1 NC
[Uimp] rated impulse withstand voltage
6 kV coil not connected to the power circuit conforming to IEC 60947
[Ui] rated insulation voltage
690 V conforming to IEC 60947-4-1
overvoltage category
III
Irms rated making capacity
650 A at 440 V AC for power circuit conforming to IEC 60947-4-1
rated breaking capacity
520 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
520 A 40 °C - 10 s for power circuit
260 A 40 °C - 60 s for power circuit
110 A 40 °C - 600 s for power circuit
associated fuse rating
10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1
125 A gG at <= 690 V coordination type 1 for power circuit
average impedance
1 mOhm - Ith 80 A 50 Hz for power circuit
power dissipation per pole
4.2 W AC-3
6.4 W AC-1
control circuit voltage limits
Operational: 0.85...1.1 Uc at 50/60 Hz (at <55 °C)
Drop-out: 0.3...0.6 Uc at 50/60 Hz (at <55 °C)
operating time
20...26 ms on closing
8...12 ms on opening
mechanical durability
5000000 cycles
maximum operating rate
1200 cyc/h 60 °C
inrush power in VA
160 VA 50 Hz cos phi 0.75 (at 20 °C)
140 VA 60 Hz cos phi 0.75 (at 20 °C)
hold-in power consumption in VA
15 VA 50 Hz cos phi 0.3 (at 20 °C)
13 VA 60 Hz cos phi 0.3 (at 20 °C)
heat dissipation
6…10 W for control circuit
minimum switching current
5 mA for control circuit
minimum switching voltage
17 V for control circuit
non-overlap time
1.5 ms on energisation guaranteed between NC and NO contact
1.5 ms on de-energisation guaranteed between NC and NO contact
insulation resistance
> 10 MOhm for control circuit
electrical durability
350000 cycles AC-1
900000 cycles AC-3
mounting support
DIN rail
Plate
connections - terminals
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 1 2.5…25 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 1 2.5…25 mm² - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 2 2.5…16 mm² - cable stiffness: solid without cable end
Recommended tightening torque
Control circuit: 1.2 N.m
Power circuit: 5 N.m
Max tightening torque
Control circuit: 1.4 N.m
Power circuit: 5.8 N.m