range of product | TeSys D TeSys D control relay TeSys F |
---|---|
range | TeSys |
product or component type | Auxiliary contact block |
auxiliary contacts operation | Instantaneous |
pole contact composition | 1 NO + 1 NC |
connections - terminals | Screw clamp terminals 1 cable 1...2.5 mm² - cable stiffness: flexible - with cable end Screw clamp terminals 1 cable 1...2.5 mm² - cable stiffness: flexible - without cable end Screw clamp terminals 1 cable 1...2.5 mm² - cable stiffness: solid - with cable end Screw clamp terminals 1 cable 1...2.5 mm² - cable stiffness: solid - without cable end Screw clamp terminals 2 cable 1...2.5 mm² - cable stiffness: flexible - with cable end Screw clamp terminals 2 cable 1...2.5 mm² - cable stiffness: flexible - without cable end Screw clamp terminals 2 cable 1...2.5 mm² - cable stiffness: solid - with cable end Screw clamp terminals 2 cable 1...2.5 mm² - cable stiffness: solid - without cable end |
mounting location | Front |
---|---|
[Ui] rated insulation voltage | 690 V - conforming to IEC 60947-5-1 600 V - certifications CSA 600 V - certifications UL |
[Ue] rated operational voltage | 690 V AC 25...400 Hz |
[Ith] conventional free air thermal current | 10 A at <= 60 °C |
Irms rated making capacity | 140 A at <= 690 V AC conforming to IEC 60947-5-1 250 A at <= 690 V DC conforming to IEC 60947-5-1 |
permissible short-time rating | 100 A at 60 °C 1 s 120 A at 60 °C 500 ms 140 A at 60 °C 100 ms |
protection type | GG fuse <= 10 A rating according to operational current for Ue <= 690 V |
associated fuse rating | 10 A gG IEC 60947-5-1 |
mechanical durability | 30 Mcycles |
minimum switching current | 5 mA |
minimum switching voltage | 17 V |
non-overlap time | 1.5 ms on de-energisation (no overlap between NC and NO contact) 1.5 ms on energisation (no overlap between NC and NO contact) |
overlap time | 1.5 ms |
insulation resistance | > 10 MOhm |
environmental characteristic | Normal environment |
---|---|
standards | BS 4794 EN 60947-5-1 IEC 60947-5-1 NF C 63-140 VDE 0660 |
product certifications | CSA UL |
IP degree of protection | IP2x conforming to VDE 0106 |
protective treatment | TH conforming to IEC 60068 |
ambient air temperature for operation | -5...60 °C |
ambient air temperature for storage | -60...80 °C |
operating altitude | 3000 m without derating |