range | TeSys |
---|---|
range of product | TeSys D |
device short name | LADN |
product or component type | Auxiliary contact block |
range compatibility | TeSys D CAD TeSys D LC1D TeSys F LC1F TeSys F CR1F |
mounting location | Front |
pole contact composition | 2 NC |
Contacts operation | Instantaneous |
[Ue] rated operational voltage | 690 V AC 25...400 Hz |
[Ui] rated insulation voltage | 690 V conforming to IEC 60947-5-1 600 V - certifications CSA 600 V - certifications UL |
[Ith] conventional free air thermal current | 10 A (at 60 °C) |
standards | EN/IEC 60947-5-1 UL 60947-5-1 CSA C22.2 No 60947-5-1 GB/T 14048.5 |
product certifications | IECEE CB Scheme UL CSA CCC EAC |
Irms rated making capacity | 140 A AC conforming to IEC 60947-5-1 250 A DC conforming to IEC 60947-5-1 |
---|---|
permissible short-time rating | 100 A 60 °C 1 s 120 A 60 °C 500 ms 140 A 60 °C 100 ms |
protection type | GG fuse 10 A |
mechanical durability | 30 Mcycles |
minimum switching current | 5 mA |
minimum switching voltage | 17 V |
non-overlap time | 1.5 ms on de-energisation no overlap between NC and NO contact 1.5 ms on energisation no overlap between NC and NO contact |
insulation resistance | > 10 MOhm |
connections - terminals | Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible without cable end Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible without cable end Screw clamp terminals 1 cable(s) 1…2.5 mm²solid Screw clamp terminals 2 cable(s) 1…2.5 mm²solid |
tightening torque | 1.7 N.m - with screwdriver flat Ø 6 mm 1.7 N.m - with screwdriver Philips No 2 |
height | 48 mm |
width | 26 mm |
depth | 42 mm |