SCHNEIDER - AUXILIARY CONTACTOR

Category: AKSESORIS
No Referensi: CAD32M7
HUBUNGI KAMI

Call / Whatsapp:


Whatsapp Only:


Tokopedia:

Main
range
TeSys
product name
TeSys CAD
product or component type
Control relay
device short name
CAD
contactor application
Control circuit
Complementary
utilisation category
DC-13
AC-14
AC-15
pole contact composition
3 NO + 2 NC
[Ue] rated operational voltage
<= 690 V AC 25...400 Hz
control circuit type
AC at 50/60 Hz
[Uc] control circuit voltage
220 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
[Ith] conventional free air thermal current
10 A (at 60 °C)
Irms rated making capacity
140 A AC conforming to IEC 60947-5-1
250 A DC conforming to IEC 60947-5-1
[Icw] rated short-time withstand current
100 A - 1 s
120 A - 500 ms
140 A - 100 ms
associated fuse rating
10 A gG conforming to IEC 60947-5-1
[Ui] rated insulation voltage
600 V UL certified
600 V CSA certified
690 V conforming to IEC 60947-5-1
mounting support
Plate
Rail
connections - terminals
Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
tightening torque
1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
control circuit voltage limits
0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
operating time
12...22 ms coil energisation and NO closing
4...12 ms coil de-energisation and NO opening
4...19 ms coil energisation and NC opening
6...17 ms coil de-energisation and NC closing
mechanical durability
30 Mcycles
maximum operating rate
180 cyc/mn
inrush power in VA
70 VA 50 Hz (at 20 °C)
hold-in power consumption in VA
8 VA 50 Hz (at 20 °C)
minimum switching voltage
17 V
minimum switching current
5 mA
non-overlap time
1.5 ms on energisation between NC and NO contact
1.5 ms on de-energisation between NC and NO contact
insulation resistance
> 10 MOhm
mechanical robustness
Shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27
Shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27
Vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
height
77 mm
width
45 mm
depth
84 mm
net weight