range | Acti 9 |
---|---|
family | Acti 9 iEM2000 |
device short name | IEM2050 |
product or component type | Energy meter |
poles description | 1P + N |
---|---|
type of measurement | Active and reactive energy Active and reactive power Power factor Current Voltage Frequency |
device application | Sub billing Multi-tariff |
accuracy class | Class 1 active energy conforming to IEC 62053-21 |
Input type | Direct input |
Rated current | 45 A |
rated voltage | 230 V - 15...10 % |
network frequency | 50 Hz |
frequency measurement range | 45…55 Hz |
technology type | Electronic |
display type | LCD display |
sampling rate | 32 samples/cycle |
measurement current | 5…45 A |
display digits | 6 |
maximum value measured | 9999.99 kWh 99999.9 kWh |
Tariff input | Tariff (2) |
communication port protocol | Modbus RTU at 1200, 2400, 4800 or 9600 bauds even/odd or none |
communication port support | Screw terminals: RS485 |
local signalling | Red LED: metering and activity 0.01, 0.1, 1, 10, 100, 1000, 2000 or 10000 p/kWh |
Digital inputs | 0 |
Digital outputs | 1 pulse |
impulse duration | 11.2...32 ms |
Supply voltage | 195...253 V AC 50 Hz |
maximum power consumption in VA | 10 VA |
maximum power consumption in W | 2 W |
[Uimp] rated impulse withstand voltage | 6 kV 1.2/50 µs |
mounting mode | Clip-on |
mounting support | DIN rail |
connections - terminals | Power circuit: tunnel type terminals (bottom) 1 8…10 mm² cable(s) Power circuit: tunnel type terminals (top) 1 8…10 mm² cable(s) Pulse output: screw clamp terminals (top) 1 2.5 mm² cable(s) Communication: screw clamp terminals (bottom) 1 2.5 mm² cable(s) |
tightening torque | Power circuit: 0.35 N.m flat screwdriver 2.2 mm Pulse output: 0.1 N.m flat screwdriver 1.3 mm Communication: 0.1 N.m flat screwdriver 1.3 mm |
wire stripping length | Power circuit: 7.5 mm Pulse output: 7 mm Communication: 7 mm |
standards | IEC 62052-11 IEC 62053-21 |
product certifications | CE |