range of product | Acti 9 |
---|---|
product name | Acti 9 iPRD |
product or component type | Surge arrester with pluggable cartridge |
device short name | IPRD40 |
device application | Distribution |
poles description | 3P + N |
remote signalling | Without |
surge arrester type | Electrical distribution network |
earthing system | TT TN-S |
surge arrester class type | Type 2 |
---|---|
surge arrester technology | MOV + GDT |
[Ue] rated operational voltage | 230/400 V AC (+/- 10 %) at 50/60 Hz |
[In] nominal discharge current | Common mode: 15 kA (L/PE) Common mode: 15 kA (N/PE) Differential mode: 15 kA (L/N) |
[Imax] maximum discharge current | Common mode: 40 kA L/PE Common mode: 40 kA N/PE Differential mode: 40 kA L/N |
[Uc] maximum continuous operating voltage | Common mode: 260 V N/PE Common mode: 350 V L/PE Differential mode: 350 V L/N |
maximum [Up] voltage protection level | Common mode <1.4 kV type 2 N/PE Differential mode <1.4 kV type 2 L/N |
[Ut] temporary overvoltage | 337 V L/N 5 s withstand 1200 V N/PE 200 ms safe failure mode 442 V L/PE 5 s withstand 1453 V L/PE 200 ms safe failure mode |
disconnector device type | Associated circuit breaker iC60H 50 A curve C - Icu 15 kA Associated circuit breaker iC60N 40 A curve C - Icu 10 kA Associated circuit breaker NG125H 63 A curve C - Icu 36 kA Associated circuit breaker NG125L 63 A curve C - Icu 50 kA Associated circuit breaker NG125N 40 A curve C - Icu 25 kA Associated fuse gG 63 A - Icu 15 kA Associated fuse gG 80 A - Icu 50 kA |
[Isccr] short-circuit current rating | 50 kA |
mounting mode | Clip-on |
mounting support | DIN rail |
9 mm pitches | 8 |
height | 85 mm |
width | 72 mm |
depth | 69 mm |
net weight | 0.414 kg |
colour | White (RAL 9003) |
response time | <= 25 ns |
[Ipe] Ground residual current | 0.003 mA 0.6 mA |
connections - terminals | Tunnel type terminal (downside) 2.5…35 mm² Tunnel type terminal (upside) 2.5…35 mm² |
tightening torque | 2.5 N.m |
standards | EN 61643-11:2012 IEC 61643-11:2011 |
---|---|
product certifications | CE |
quality labels | KEMA-KEUR NF |
IP degree of protection | IP40 on front face: conforming to IEC 60529 IP20 built-in: conforming to IEC 60529 |
IK degree of protection | IK03 conforming to IEC 62262 |
relative humidity | 5…95 % |
operating altitude | 2000 m |
ambient air temperature for operation | -25…60 °C |
ambient air temperature for storage | -40…85 °C |