device application | Distribution |
---|---|
range | Acti 9 |
product name | Acti 9 iC60 |
product or component type | Miniature circuit-breaker |
device short name | IC60L |
poles description | 3P |
number of protected poles | 3 |
[In] rated current | 16 A |
network type | AC DC |
trip unit technology | Thermal-magnetic |
curve code | C |
breaking capacity | 20 kA Icu conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 25 kA Icu conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 50 kA Icu conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 70 kA Icu conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz 70 kA Icu conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz 15000 A Icn conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz 20 kA Icu conforming to EN/IEC 60947-2 - <= 180 V DC |
utilisation category | Category A conforming to EN 60947-2 Category A conforming to IEC 60947-2 |
suitability for isolation | Yes conforming to EN 60947-2 Yes conforming to IEC 60947-2 Yes conforming to EN 60898-1 Yes conforming to IEC 60898-1 |
standards | EN 60898-1 EN 60947-2 IEC 60898-1 IEC 60947-2 |
network frequency | 50/60 Hz |
---|---|
magnetic tripping limit | 8 x In +/- 20 % |
[Ics] rated service breaking capacity | 35 kA 50 % x Icu conforming to EN 60947-2 - 12...133 V AC 50/60 Hz 35 kA 50 % x Icu conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz 20 kA 100 % x Icu conforming to EN 60947-2 - 125...180 V DC 20 kA 100 % x Icu conforming to IEC 60947-2 - 125...180 V DC 7500 A 50 % x Icu conforming to EN 60898-1 - 400 V AC 50/60 Hz 7500 A 50 % x Icu conforming to IEC 60898-1 - 400 V AC 50/60 Hz 25 kA 50 % x Icu conforming to EN 60947-2 - 220...240 V AC 50/60 Hz 12.5 kA 50 % x Icu conforming to EN 60947-2 - 380...415 V AC 50/60 Hz 10 kA 50 % x Icu conforming to EN 60947-2 - 440 V AC 50/60 Hz 25 kA 50 % x Icu conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz 12.5 kA 50 % x Icu conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz 10 kA 50 % x Icu conforming to IEC 60947-2 - 440 V AC 50/60 Hz |
limitation class | 3 conforming to EN 60898-1 3 conforming to IEC 60898-1 |
[Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to IEC 60947-2 500 V AC 50/60 Hz conforming to EN 60947-2 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to EN 60947-2 6 kV conforming to IEC 60947-2 |
contact position indicator | Yes |
control type | Toggle |
local signalling | Trip indicator |
mounting mode | Fixed |
mounting support | DIN rail |
comb busbar and distribution block compatibility | YES top or bottom |
9 mm pitches | 6 |
height | 85 mm |
width | 54 mm |
depth | 78.5 mm |
product weight | 0.375 kg |
colour | White |
mechanical durability | 20000 cycles |
electrical durability | 10000 cycles |
connections - terminals | Single terminal, top or bottom rigid wire(s) 1...25 mm² max Single terminal, top or bottom flexible wire(s) 1...16 mm² max |
wire stripping length | 14 mm top or bottom |
tightening torque | 2 N.m top or bottom |
earth-leakage protection | Separate block |
IP degree of protection | IP20 conforming to EN 60529 IP20 conforming to IEC 60529 |
---|---|
pollution degree | 3 conforming to EN 60947-2 3 conforming to IEC 60947-2 |
overvoltage category | IV |
tropicalisation | 2 conforming to IEC 60068-1 |
relative humidity | 95 % ( 55 °C ) |
operating altitude | 0...2000 m |
ambient air temperature for operation | -35...70 °C |
ambient air temperature for storage | -40...85 °C |