SCHNEIDER - ACTI9 IC60N 2P C 6A MCB

Category: ACTI9
No Referensi: A9F74206
HUBUNGI KAMI

Call / Whatsapp:


Whatsapp Only:


Tokopedia:

Main
device application
Distribution
range
Acti 9
product name
Acti 9 iC60
product or component type
Miniature circuit-breaker
device short name
IC60N
poles description
2P
number of protected poles
2
[In] rated current
6 A
network type
AC
DC
trip unit technology
Thermal-magnetic
curve code
C
breaking capacity
6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
36 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2
utilisation category
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2
suitability for isolation
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2
standards
EN 60898-1
IEC 60898-1
EN 60947-2
IEC 60947-2
Complementary
network frequency
50/60 Hz
magnetic tripping limit
8 x In +/- 20 %
[Ics] rated service breaking capacity
15 kA 75 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz
7.5 kA 75 % conforming to EN 60947-2 - 380...415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN 60947-2 - 440 V AC 50/60 Hz
15 kA 75 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz
7.5 kA 75 % conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz
4.5 kA 75 % conforming to IEC 60947-2 - 440 V AC 50/60 Hz
27 kA 75 % conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz
27 kA 75 % conforming to EN 60947-2 - 12...133 V AC 50/60 Hz
6000 A 100 % conforming to EN 60898-1 - 400 V AC 50/60 Hz
6000 A 100 % conforming to IEC 60898-1 - 400 V AC 50/60 Hz
10 kA 100 % conforming to IEC 60947-2 - 72...125 V DC
10 kA 100 % conforming to EN 60947-2 - 72...125 V DC
limitation class
3 conforming to EN 60898-1
3 conforming to IEC 60898-1
[Ui] rated insulation voltage
500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2
contact position indicator
Yes
control type
Toggle
local signalling
Trip indicator
mounting mode
Fixed
mounting support
DIN rail
comb busbar and distribution block compatibility
Top or bottom: YES
9 mm pitches
4
height
85 mm
width
36 mm
depth
78.5 mm
net weight
0.25 kg
colour
White
mechanical durability
20000 cycles
electrical durability
10000 cycles
connections - terminals
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible
wire stripping length
14 mm for top or bottom connection
tightening torque
2 N.m top or bottom
earth-leakage protection
Separate block