range | Compact |
---|---|
range of product | NS630b...1600 |
product or component type | Circuit breaker |
device short name | Compact NS800H |
device application | Distribution |
poles description | 4P |
protected poles description | 3t |
network type | AC |
breaking capacity code | H |
suitability for isolation | Yes conforming to IEC 60947-2 |
utilisation category | Category B |
trip unit name | Micrologic 2.0 |
trip unit technology | Electronic |
trip unit rating | 800 A at 50 °C |
network frequency | 50/60 Hz |
---|---|
control type | Toggle Rotary handle |
mounting mode | Fixed |
mounting support | Backplate |
upside connection | Front |
downside connection | Front |
(In) rated current up to 65 °C | 800 A at 50 °C |
[Ui] rated insulation voltage | 800 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
[Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
circuit breaker CT rating | 800 A |
breaking capacity | 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ics] rated service breaking capacity | 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
auxiliary contact composition | 1 NO/NC |
mechanical durability | 10000 cycles |
electrical durability | 2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 4000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 5000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 6000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2 |
local signalling | Positive contact indication |
[Icw] rated short-time withstand current | 19.2 kA |
trip unit protection functions | LI |
protection type | Instantaneous short-circuit protection Overload protection (long time) |
long time pick-up adjustment type Ir | Adjustable |
long time pick-up adjustment range | 0.4...1 x In |
long time delay adjustment type | Adjustable 9 settings |
[tr] long-time delay adjustment range | 0.7…16.6 s 7.2 x Ir 12.5…600 s 1.5 x Ir 0.5…24 s 6 x Ir |
thermal memory | 20 mn |
instantaneous pick-up adjustment type Ii | Adjustable |
instantaneous pick-up adjustment range | 1.5...10 x Ir |
integrated instantaneous protection | 40 kA |
height | 327 mm |
width | 210 mm |
depth | 147 mm |
standards | IEC 60947-2 |
---|---|
product certifications | ASEFA ASTA |
power losses | 15 W |
IP degree of protection | IP40 conforming to IEC 60529 |
IK degree of protection | IK07 conforming to EN 50102 |
pollution degree | 3 conforming to IEC 60947 |
ambient air temperature for operation | -25…70 °C |
ambient air temperature for storage | -50…85 °C |